When does a room need two exits? — SBC 201
A room or space needs two exits or exit access doorways when its occupant load or its common path of egress travel distance exceeds Table 1006.2.1 (SBC 201, clause 1006.2.1). For example: more than 49 occupants in Groups A, B, E, F, M and U, more than 29 in S, more than 20 in R-2.
| Occupancy | Maximum occupant load with one exit | Common path, no sprinklers: load of 30 or less | Common path, no sprinklers: load over 30 | Common path, sprinklered |
|---|---|---|---|---|
| A, E, M | 49 | 23 m | 23 m | 23 m |
| B | 49 | 30 m | 23 m | 30 m |
| F | 49 | 23 m | 23 m | 30 m |
| H-1, H-2, H-3 | 3 | Not permitted | Not permitted | 7.5 m |
| H-4, H-5 | 10 | Not permitted | Not permitted | 23 m |
| I-1, I-2, I-4 | 10 | Not permitted | Not permitted | 23 m |
| I-3 | 10 | Not permitted | Not permitted | 30 m |
| R-1 | 10 | Not permitted | Not permitted | 23 m |
| R-2 | 20 | Not permitted | Not permitted | 38 m |
| R-3, R-4 | 20 | Not permitted | Not permitted | 38 m |
| S | 29 | 30 m | 23 m | 30 m |
| U | 49 | 30 m | 23 m | 23 m |
Exceeding either limit is enough: the design occupant load, or the common path of egress travel distance. The cumulative occupant load from adjacent rooms is worked out under Section 1004.2.
The sprinklered column is for buildings equipped throughout with an automatic sprinkler system under Section 903.3.1.1 or 903.3.1.2, and for Group H under Section 903.2.5. "Not permitted" means the table gives this group no value without sprinklers.
The table has footnotes for: assembly rooms with fixed seating (Section 1030.8), Group I-2 (Section 407.4), Groups R-3 and R-4, and Group S-2 open parking garages, where the common path is at most 30 m. Read the footnotes before you use a value.
The clause has three exceptions; one is that unoccupied mechanical rooms need not meet the common path measurement.
Read clause 1006.2.1 in the code reader
General educational content (ref: SBC 201 §1006.2.1) — pending licensed-engineer review; not an official certification. Always rely on the official code text.