Stair riser height and tread depth — SBC 201

In SBC 201 (clause 1011.5.2) a stair riser is at most 175 mm and at least 100 mm high, and a tread is at least 275 mm deep. Inside dwellings (Group R-3 and within dwelling units in Group R-2) the riser may be up to 200 mm and the tread at least 250 mm.

ItemGeneral ruleDwellings (Exception 3)
Maximum riser height175 mm200 mm
Minimum riser height100 mmnot stated in the exception
Minimum tread depth275 mm250 mm
Winder tread at the walkline275 mm250 mm
Winder tread, smallest depth250 mm150 mm

The riser is measured vertically between the nosings of adjacent treads, or between the landing and the adjacent tread. The tread depth is measured horizontally between the vertical planes of the foremost projection of adjacent treads, at a right angle to the tread's nosing.

Exception 3 covers Group R-3, dwelling units in Group R-2, and Group U occupancies accessory to them. Where such a stair has solid risers and a tread less than 275 mm deep, it needs a nosing projection of at least 20 mm and at most 32 mm.

Winder treads are measured at the walkline, and their smallest depth within the clear width of the stair is the one in the table. The clause has other exceptions: spiral stairways follow Section 1011.10, and stairways connecting stepped aisles to cross aisles follow Section 1030.14.2. Read the clause with its exceptions before you settle a design.

Read clause 1011.5.2 in the code reader

General educational content (ref: SBC 201 §1011.5.2) — pending licensed-engineer review; not an official certification. Always rely on the official code text.