Stair riser height and tread depth — SBC 201
In SBC 201 (clause 1011.5.2) a stair riser is at most 175 mm and at least 100 mm high, and a tread is at least 275 mm deep. Inside dwellings (Group R-3 and within dwelling units in Group R-2) the riser may be up to 200 mm and the tread at least 250 mm.
| Item | General rule | Dwellings (Exception 3) |
|---|---|---|
| Maximum riser height | 175 mm | 200 mm |
| Minimum riser height | 100 mm | not stated in the exception |
| Minimum tread depth | 275 mm | 250 mm |
| Winder tread at the walkline | 275 mm | 250 mm |
| Winder tread, smallest depth | 250 mm | 150 mm |
The riser is measured vertically between the nosings of adjacent treads, or between the landing and the adjacent tread. The tread depth is measured horizontally between the vertical planes of the foremost projection of adjacent treads, at a right angle to the tread's nosing.
Exception 3 covers Group R-3, dwelling units in Group R-2, and Group U occupancies accessory to them. Where such a stair has solid risers and a tread less than 275 mm deep, it needs a nosing projection of at least 20 mm and at most 32 mm.
Winder treads are measured at the walkline, and their smallest depth within the clear width of the stair is the one in the table. The clause has other exceptions: spiral stairways follow Section 1011.10, and stairways connecting stepped aisles to cross aisles follow Section 1030.14.2. Read the clause with its exceptions before you settle a design.
Read clause 1011.5.2 in the code reader
General educational content (ref: SBC 201 §1011.5.2) — pending licensed-engineer review; not an official certification. Always rely on the official code text.