← Guides

Minimum room area — SBC 201

In SBC 201 (clause 1208.3) every dwelling unit needs at least one room with a net floor area of not less than 11.2 m2, and every other habitable room needs not less than 6.5 m2. Kitchens are not required to have a minimum floor area.

ItemMinimumReference
At least one room in every dwelling unit11.2 m2 net floor area1208.3
Other habitable rooms6.5 m2 net floor area1208.3
Kitchensno minimum floor area1208.3, Exception
Smallest plan dimension of a habitable space (other than a kitchen)2100 mm1208.1
Clear passageway in a kitchen between counter fronts and appliances or walls900 mm1208.1

The area meant is the room's net floor area. The clause is about dwelling units: at least one room at the larger figure, and the other habitable rooms at the smaller one.

Area is not the only test: clause 1208.1 requires every plan dimension of a habitable space, other than a kitchen, to be not less than 2100 mm. A 6.5 m2 room narrower than 2100 mm does not meet it.

In a room with a sloped ceiling, any part measuring less than 1500 mm from the finished floor to the ceiling is left out of the minimum-area calculation (clause 1208.2, Exception 2).

Efficiency dwelling units have their own rule in clause 1208.4; read it in the code text.

Read clause 1208.3 in the code reader

General educational content (ref: SBC 201 §1208.3) — pending licensed-engineer review; not an official certification. Always rely on the official code text.