Minimum ceiling height — SBC 201
The minimum ceiling height in SBC 201 (clause 1208.2) is 2250 mm above the finished floor in occupiable spaces, habitable spaces and corridors, and 2100 mm in bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms.
| Space or case | Value | Reference |
|---|---|---|
| Occupiable spaces, habitable spaces and corridors | 2250 mm | 1208.2 |
| Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms | 2100 mm | 1208.2 |
| Corridors within a dwelling unit or sleeping unit in Group R | 2100 mm | Exception 4 |
| Beams or girders below the required height in one- and two-family dwellings (spaced at least 1200 mm on center) | at most 150 mm | Exception 1 |
| Sloped ceiling: parts not counted in the room's minimum area | anything lower than 1500 mm | Exception 2 |
The height is measured from the finished floor to the ceiling. The 2250 mm and 2100 mm figures are the least the code accepts.
In a room with a sloped ceiling the required height is needed in one-half of its area, and any part lower than 1500 mm is left out of the room's minimum-area calculation (Exception 2).
The height of mezzanines and the spaces below them follows Section 505.1 (Exception 3). Stairways have their own headroom rule in clause 1011.3.
Read clause 1208.2 in the code reader
General educational content (ref: SBC 201 §1208.2) — pending licensed-engineer review; not an official certification. Always rely on the official code text.