Means of egress width — SBC 201

In SBC 201 a door needs a clear opening at least 800 mm wide (clause 1010.1.1) and a stairway is at least 1100 mm wide (clause 1011.2). On top of that, capacity is worked out from the occupant load: 7.6 mm per occupant for stairways (clause 1005.3.1) and 5.08 mm per occupant for other egress components (clause 1005.3.2).

ComponentMinimum widthCapacity factorClause
Door800 mm clear opening5.08 mm per occupant1010.1.1, 1005.3.2
Stairway1100 mm (900 mm where the occupant load is less than 50)7.6 mm per occupant1011.2, 1005.3.1
Corridoras given in Table 1020.3 of the code5.08 mm per occupant1020.3, 1005.3.2

The width each component needs is the larger of two numbers: its minimum, and the capacity worked out. Example: a story with an occupant load of 300 needs 300 × 5.08 = 1524 mm of doors and 300 × 7.6 = 2280 mm of stairways. Where a stairway serves more than one story, each story's occupant load is taken on its own.

In buildings, other than Groups H and I-2, equipped throughout with an automatic sprinkler system under Section 903.3.1.1 or 903.3.1.2 and an emergency voice/alarm communication system under Section 907.5.2.2, the factor drops to 5.08 mm per occupant for stairways and to 3.8 mm per occupant for other components (Exception 1 of each clause).

A door's clear opening width is measured between the face of the door and the stop, with the door open 90 degrees. The clear opening height of a door is at least 2000 mm.

The minimum corridor width is set by clause 1020.3 and its table, by type of occupancy; read the value there. A corridor's capacity is worked out like the other components that are not stairways.

Read clause 1005.3 in the code reader

General educational content (ref: SBC 201 §1005.3) — pending licensed-engineer review; not an official certification. Always rely on the official code text.