Means of egress width — SBC 201
In SBC 201 a door needs a clear opening at least 800 mm wide (clause 1010.1.1) and a stairway is at least 1100 mm wide (clause 1011.2). On top of that, capacity is worked out from the occupant load: 7.6 mm per occupant for stairways (clause 1005.3.1) and 5.08 mm per occupant for other egress components (clause 1005.3.2).
| Component | Minimum width | Capacity factor | Clause |
|---|---|---|---|
| Door | 800 mm clear opening | 5.08 mm per occupant | 1010.1.1, 1005.3.2 |
| Stairway | 1100 mm (900 mm where the occupant load is less than 50) | 7.6 mm per occupant | 1011.2, 1005.3.1 |
| Corridor | as given in Table 1020.3 of the code | 5.08 mm per occupant | 1020.3, 1005.3.2 |
The width each component needs is the larger of two numbers: its minimum, and the capacity worked out. Example: a story with an occupant load of 300 needs 300 × 5.08 = 1524 mm of doors and 300 × 7.6 = 2280 mm of stairways. Where a stairway serves more than one story, each story's occupant load is taken on its own.
In buildings, other than Groups H and I-2, equipped throughout with an automatic sprinkler system under Section 903.3.1.1 or 903.3.1.2 and an emergency voice/alarm communication system under Section 907.5.2.2, the factor drops to 5.08 mm per occupant for stairways and to 3.8 mm per occupant for other components (Exception 1 of each clause).
A door's clear opening width is measured between the face of the door and the stop, with the door open 90 degrees. The clear opening height of a door is at least 2000 mm.
The minimum corridor width is set by clause 1020.3 and its table, by type of occupancy; read the value there. A corridor's capacity is worked out like the other components that are not stairways.
Read clause 1005.3 in the code reader
General educational content (ref: SBC 201 §1005.3) — pending licensed-engineer review; not an official certification. Always rely on the official code text.