Fire apparatus access road width — SBC 801

A fire apparatus access road needs an unobstructed width of at least 6 m, not counting shoulders, and an unobstructed vertical clearance of at least 4 m (SBC 801, clause 503.2.1). The road must reach to within 45 m of all portions of the exterior walls of the first story (clause 503.1.1).

ItemValueClause
Unobstructed width (shoulders excluded)at least 6 m503.2.1
Vertical clearanceat least 4 m503.2.1
Reach to any portion of the buildingwithin 45 m503.1.1
A dead-end road that needs a turnaroundlonger than 45 m503.2.5
Turning radiusset by the Fire official503.2.4
Distance from a hydrant beyond which on-site hydrants are called formore than 120 m507.5.1
The same distance for Groups R-3 and U, or a building sprinklered throughout180 m507.5.1, Exceptions 1 and 2

The 45 m is measured along an approved route around the outside of the building, and it covers all portions of the facility and all portions of the exterior walls of the first story. Approved security gates under Section 503.6 are excepted from the width.

The Fire official may increase the 45 m in set cases, among them: the building is equipped throughout with an approved automatic sprinkler system, or there are not more than two Group R-3 or Group U occupancies (clause 503.1.1, Exception 1).

Hydrants: where a portion of the building is more than 120 m from a hydrant on a fire apparatus access road, measured along an approved route around the building, on-site hydrants and mains are provided where the Fire official requires them (clause 507.5.1).