Saudi Building Code door requirements — SBC 201

In SBC 201 (clause 1010.1.1) a door in the means of egress needs a clear opening at least 800 mm wide and 2000 mm high. A door serving a room with an occupant load of 50 or more, or a Group H occupancy, swings in the direction of egress travel (clause 1010.1.2.1).

RequirementValueClause
Clear opening widthat least 800 mm1010.1.1
Clear opening heightat least 2000 mm1010.1.1
Group I-2 egress doors used for the movement of bedsat least 1000 mm1010.1.1
Swing in the direction of egress traveloccupant load of 50 or more, or Group H1010.1.2.1
Force to unlatch67 N by push or pull; 3.15 N-m by rotation1010.1.3
Force to open an interior swinging egress door, manual and not fire ratedat most 22 N1010.1.3
Other doors, and doors required to be fire rated133 N to set in motion and 67 N to reach full-open1010.1.3
Threshold height12.5 mm; 20 mm for sliding doors serving dwelling units1010.1.6
Landing length at a door, in the direction of travelat least 1100 mm1010.1.5
Space between two doors in a series1200 mm plus the width of a door swinging into the space1010.1.7
Height of handles and locks above the finished floor850 mm to 1200 mm1010.2.3

These are the requirements for doors in the means of egress (clause 1010.1 onward). The clear width is measured between the face of the door and the stop, with the door open 90 degrees. Where an opening has two leaves without a mullion, one leaf must give a clear width of at least 800 mm.

Door type: egress doors are side-hinged swinging, pivoted or balanced doors (clause 1010.1.2). The exceptions include doors within or serving a single dwelling unit in Groups R-2 and R-3, and private garages, office areas, factory and storage areas with an occupant load of 10 or less.

Floor and threshold: a floor or landing is needed on each side of a door, at the same elevation (clause 1010.1.4). A fully open door must not reduce a required dimension by more than 175 mm (clause 1010.1.5). A raised threshold or floor level change greater than 6 mm at a doorway is beveled with a slope of at most one unit vertical in two units horizontal (clause 1010.1.6).

Size exceptions in clause 1010.1.1 include: 700 mm for doors to Group I-3 resident sleeping units not required to be Accessible; 500 mm for doors to nonaccessible single-user shower compartments, toilet stalls and changing rooms; and a 1900 mm height for exterior doors, other than the required exit door, in dwelling and sleeping units not required to be Accessible, Type A or Type B units. Unlatching a door takes not more than one motion (clause 1010.2.1).

This guide does not cover fire-resistance ratings of doors; those are in Section 716 of SBC 201.

Read clause 1010.1.1 in the code reader

General educational content (ref: SBC 201 §1010.1.1) — pending licensed-engineer review; not an official certification. Always rely on the official code text.