Maximum dead-end corridor length — SBC 201

A dead-end corridor may not be longer than 6 m where more than one exit or exit access doorway is required (SBC 201, clause 1020.5). The limit rises to 15 m in Groups B, E, F, I-1, M, R-1, R-2, S and U where the building is sprinklered throughout.

CaseMaximum lengthReference
General rule6 m1020.5
Groups B, E, F, I-1, M, R-1, R-2, S and U, sprinklered throughout under 903.3.1.115 mException 2
Group I-3, Conditions 2, 3 and 415 mException 1
Group I-2, Condition 2: dead ends not serving patient rooms or patient treatment spaces9 mException 4
The dead end is shorter than 2.5 times its least widthnot limitedException 3

The rule applies where more than one exit or exit access doorway is required: the exit access is arranged so that no dead-end corridor is longer than the limit.

Exception 3 helps with short pockets: a dead end shorter than 2.5 times its least width is not limited in length. Example: a dead end whose least width is 1.5 m is not limited while it is shorter than 2.5 × 1.5 = 3.75 m.

The 15 m in Exception 2 depends on the whole building having an automatic sprinkler system under Section 903.3.1.1, and it covers the listed groups only; other groups stay at 6 m unless another exception covers them.

Read clause 1020.5 in the code reader

General educational content (ref: SBC 201 §1020.5) — pending licensed-engineer review; not an official certification. Always rely on the official code text.