Maximum dead-end corridor length — SBC 201
A dead-end corridor may not be longer than 6 m where more than one exit or exit access doorway is required (SBC 201, clause 1020.5). The limit rises to 15 m in Groups B, E, F, I-1, M, R-1, R-2, S and U where the building is sprinklered throughout.
| Case | Maximum length | Reference |
|---|---|---|
| General rule | 6 m | 1020.5 |
| Groups B, E, F, I-1, M, R-1, R-2, S and U, sprinklered throughout under 903.3.1.1 | 15 m | Exception 2 |
| Group I-3, Conditions 2, 3 and 4 | 15 m | Exception 1 |
| Group I-2, Condition 2: dead ends not serving patient rooms or patient treatment spaces | 9 m | Exception 4 |
| The dead end is shorter than 2.5 times its least width | not limited | Exception 3 |
The rule applies where more than one exit or exit access doorway is required: the exit access is arranged so that no dead-end corridor is longer than the limit.
Exception 3 helps with short pockets: a dead end shorter than 2.5 times its least width is not limited in length. Example: a dead end whose least width is 1.5 m is not limited while it is shorter than 2.5 × 1.5 = 3.75 m.
The 15 m in Exception 2 depends on the whole building having an automatic sprinkler system under Section 903.3.1.1, and it covers the listed groups only; other groups stay at 6 m unless another exception covers them.
Read clause 1020.5 in the code reader
General educational content (ref: SBC 201 §1020.5) — pending licensed-engineer review; not an official certification. Always rely on the official code text.