910.3.2 Smoke and heat vent locations.
SBC 801 · Edition 2024 · p. 221
Smoke and heat vents shall be located 6 m or more from adjacent lot lines and fire walls and 3000 mm or more from fire barriers. Vents shall be uniformly located within the roof in the areas of the building…