905.3.4 Exception
SBC 801 · Edition 2024 · p. 192
Where the building or area is equipped throughout with an automatic sprinkler system, a 40 mm hose connection shall be installed in accordance with NFPA 13 or in accordance with NFPA 14 for Class II or III standpipes.