1026.2 Exception
SBC 801 · Edition 2024 · p. 284
A fire-resistance rating is not required at horizontal exits between a building area and an above-grade pedestrian walkway constructed in accordance with Section 3104 of SBC 201, provided that the distance between connected buildings is more than 6000 mm. Horizontal…