711.1 Horizontal Branch Connections Above or Below Offsets of Vertical Pipe Stacks:

SBC 701 · Edition 2024 · p. 73

Where a horizontal branch connects to the stack above or below 600 mm of the vertical collector, the offset shall be located more than four branch intervals below the top of the vertical collector and the offset shall be vented…