7.7.9 Calculation of (Vc) for Pretensioned Members in Regions of Reduced Prestressing Force
SBC 312 · Edition 2024 · p. 115
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 7.7.9.1 In computing (Vc), the transfer length of prestressed reinforcement (ltr) shall be assumed equal to (50db) for strands and equal to (100db) for wire.
- 7.7.9.2 Where bonding of strands extends to the end of the member, the effective prestress force shall be assumed to increase linearly from zero at the end of the prestressed reinforcement to a maximum value at a distance (ltr) from the end of the prestressed reinforcement.
- 7.7.9.3 At locations corresponding to the reduced effective prestress force given in (Section 7.7.9.2), (Vc) shall be calculated in accordance with the requirements of (Section 7.7.9.3).
- 7.7.9.4 Where bonding of strands does not extend to the end of the member, the effective prestress force shall be assumed to increase linearly from zero at the point where bonding begins to a maximum value at a distance (ltr) from the point.
- 7.7.9.5 At locations corresponding to the reduced effective prestress force given in (Section 7.7.9.4), (Vc) shall be calculated in accordance with the requirements of (Section 7.7.9.5).