14.3.1 General
SBC 312 · Edition 2024 · p. 186
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 14.3.1.1 Transfer of forces is permitted by means of grouted joints, or by bearing, or shear keys, or anchors, or mechanical connections, or reinforcement, or any combination of the foregoing.
- 14.3.1.2 Connections shall be verified for adequacy by analysis or testing.
- 14.3.1.3 Connection details that rely solely on friction generated by gravity loads shall not be permitted.
- 14.3.1.4 Connections and regions adjacent to them shall be designed to resist forces and accommodate deformations resulting from all load effects in the precast structural system.
- 14.3.1.5 The structural effects of restraints to volume change, consistent with the requirements of Section 5.3.6, SBC 304, shall be considered in the design of connections.
- 14.3.1.6 The effects of tolerances specified for the purpose of manufacturing and erecting precast members shall be considered when designing connections.
- 14.3.1.7
- 14.3.1.8 Structural integrity ties shall be provided in the vertical, longitudinal, and transverse directions and around the perimeter of the structure in conformance with the requirements of Section 14.3.4 or 14.3.5.