27.2.5 If the structure under investigation does not satisfy the conditions or criteria given in (Sections 27.3 or 27.5), the structure is permitted to be used at a lower load rating based on the results of the load test or the results of analysis, and subject to obtaining the approval of the building official.

SBC 311 · Edition 2024 · p. 157

These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.

Read the full clause
SBC 311 27.2.5: If the structure under investigation does not satisfy the conditions or criteria given in (Sections 27.3 or 27.5), the structure is permitted to be used at a lower load rating based on the results of the load test or the results of analysis, and subject to obtaining the approval of the building official. | Emtithal