25.5.2 Lap Splice Length of Glass Fiber-Reinforced Polymer Bars Subjected to Tension
SBC 311 · Edition 2024 · p. 137
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 25.5.2.1 The splice length in tension (l_st) for bars subjected to tension shall be in accordance with the requirements of (Section 25.5.2.1), where the value of (l_d) is calculated in accordance with the requirements of (Section 25.4.2.1 (a)).
- 25.5.2.2 Where the sizes of the bars in a splice subjected to tension are different, the splice length shall be the splice length resulting from the larger reinforcing bar.