25.2.3

SBC 311 · Edition 2024 · p. 133

The clear spacing between longitudinal reinforcement bars in columns, pedestals, struts, and boundary elements in walls shall be not less than the greatest of: (38) mm, (1.5) times the bar diameter (d_b), (4/3) times the diameter of the aggregate used.