24.4.3 Reinforcement with Glass Fiber-Reinforced Polymer Bars
SBC 311 · Edition 2024 · p. 131
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 24.4.3.1 Reinforcement resisting stresses due to shrinkage and temperature shall conform to the requirements of (Section 20.2.1.4), and shall also conform to the requirements of (Section 24.4.3.2 through 24.4.3.5).
- 24.4.3.2 The ratio of the area of shrinkage and temperature reinforcement to the gross area of concrete shall not be less than (140/E_f).
- 24.4.3.3 The spacing of shrinkage and temperature reinforcement bars shall not exceed the lesser of: (3h) and (300) mm.
- 24.4.3.4 At all sections, if required, the reinforcement used to resist shrinkage and temperature stresses shall develop (0.006 E_f) in tension in accordance with the requirements of (Section 25.4.2).
- 24.4.3.5 Shrinkage and temperature reinforcement shall not be required perpendicular to the flexural reinforcement where the conditions given in (Section 24.4.3.5) are satisfied, for one-way precast slabs and wall panels.