20.6 Embedments
SBC 311 · Edition 2024 · p. 114
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 20.6.1 Embedments shall not significantly impair the strength of the structure and shall not reduce fire protection.
- 20.6.2 The materials of embedments shall not be harmful to the concrete or the reinforcement.
- 20.6.3 Embedments made of aluminum shall be painted or covered to prevent reaction between the aluminum and the concrete.
- 20.6.4 Reinforcement with an area not less than (1650/E_f) times the area of the concrete section shall be provided perpendicular to the pipe embedments.
- 20.6.5 The specified concrete cover for pipe embedments with their fittings shall be at least (38) mm for concrete resting on the ground or exposed to weather, and at least (19) mm for concrete not exposed to weather or not in contact with the ground.