16.3.4 Minimum Reinforcement with Glass Fiber-Reinforced Polymer Bars for Connections Between Cast-in-Place Structural Members and Foundations
SBC 311 · Edition 2024 · p. 104
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 16.3.4.1 The area of reinforcement (A_f) for structural connections between cast-in-place columns or piers/pedestals and footings shall not be less than (0.01A_g), where (A_g) is the gross area of the supported member.
- 16.3.4.2 The vertical reinforcement area of structural connections between cast-in-place walls and foundations shall satisfy the requirements of Section 11.6.1.