11.7.2 Spacings of Glass Fiber-Reinforced Polymer Bars
SBC 311 · Edition 2024 · p. 90
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 11.7.2.1 The spacing of longitudinal bars in walls shall not exceed (3h) or (300) mm, whichever is less, and the spacing of longitudinal bars shall not exceed (lw/3) where shear reinforcement is required.
- 11.7.2.2 Intentionally left blank.
- 11.7.2.3 Reinforcing bars for walls with a height (h) greater than (250) mm, except basement walls and cantilever retaining walls, shall be distributed in two layers, and the reinforcement for each direction shall be placed in two layers, one near each face.
- 11.7.2.4 Tension reinforcement shall be suitably distributed so that it is as close as practicable to the tension face.