13.6.7 Distribution Systems: Piping Systems
SBC 301 · Edition 2024 · p. 99
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 13.6.7.1 Piping systems shall be designed for the seismic forces and seismic relative displacements in accordance with the requirements of (Section 13.3), unless otherwise stated in (Section 13.6.7).
- 13.6.7.2 Pressure piping systems (ASME) shall meet the requirements of Section 13.6.7.9.
- 13.6.7.3 Fire protection sprinkler pipes shall meet the requirements in Section 13.6.7.10.
- 13.6.7.4 Elevator system pipes shall meet the requirements of Section 13.6.11.
- 13.6.7.5 Where applicable material standards or recognized design rules are not used, piping design shall include consideration of service loads, on the basis of the allowable stresses given in (Section 13.6.7.5).
- 13.6.7.6 Piping not detailed to accommodate the seismic relative displacements at connections to other components shall be provided with connections having sufficient flexibility to avoid failure of the connection between the components.
- 13.6.7.7 Suspended components that are installed in a single line and are rigidly connected to and supported by the piping system are permitted to be considered part of the piping system for the purposes of determining the required size of lateral bracing.
- 13.6.7.8 Where components are independently supported because of their weight but the piping connected to them is not supported, flexibility shall be provided as necessary to accommodate the relative movement between the components.
- 13.6.7.9 Pressure Piping Systems (ASME)
- 13.6.7.10 Fire Protection Sprinkler Pipe Systems
- 13.6.7.11