903.4 Sprinkler system supervision and alarms.
SBC 201 · Edition 2024 · p. 317
Valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures and waterflow switches on all sprinkler systems shall be electrically supervised by a listed fire alarm control unit.