705.8.4 Mixed openings.

SBC 201 · Edition 2024 · p. 184

Where both unprotected and protected openings are located in the exterior wall in any story of a building, the total area of openings shall be determined in accordance with the following: (7-2) (Ap/ap) + (Au/au) ≤ 1 where: Ap=Actual area…