412.3.6.2 Separation of maximum single fire areas.

SBC 201 · Edition 2024 · p. 122

Maximum single fire areas established in accordance with hangar classification and construction type in TABLE 412.3.6 shall be separated by 2-hour fire walls constructed in accordance with Section 706. In determining the maximum single fire area as set forth in…