3313.5 Standpipe supply.

SBC 201 · Edition 2024 · p. 693

Regardless of the presence of combustible building materials, the construction type or the fire separation distance, where a standpipe is required in accordance with Section 3311, a water supply providing a minimum flow of 1900 L/m shall be provided. The…