2111.7 Firebox dimensions
SBC 201 · Edition 2024 · p. 563
The firebox of a concrete or masonry fireplace shall have a minimum depth of 500 mm. The throat shall be not less than 200 mm above the fireplace opening. The throat opening shall not be less than 100 mm in…