1709.3.1 Test procedure.

SBC 201 · Edition 2024 · p. 543

The test assembly shall be subjected to an increasing superimposed load equal to not less than two times the superimposed design load. The test load shall be left in place for a period of 24 hours. The tested assembly shall…