712.2 Design Limits
SBC 1101 · Edition 2024 · p. 261
These are the clause's opening lines. The full clause, with its tables and exceptions, opens in the code reader.
Read the full clauseUnder this clause
- 712.2.1 The thickness of the backfill layer shall be determined in accordance with the requirements of Section 712.2.1. The backfill materials shall also include compacted materials made of crushed stone or gravel with an appropriate mixture of fine materials.
- 712.2.2 The thickness of the floor slab shall be determined in accordance with the requirements of Section 712.2.2.
- 712.2.3 Contraction joints shall be used to ensure regular cracking due to shrinkage and temperature changes. They shall be sawn or formed and shall extend at least one-quarter of the slab thickness.
- 712.2.4 The spacing between the two directions at the joint shall comply with the requirements of Section 712.2.4. The reinforcement, where required, shall also be continuous across the joint.
- 712.2.5 The area of a slab panel shall not exceed 30 m2, nor shall the long side exceed the short side by more than 25 %.